Henan Xuchang Sunlight Electric and Optical Cables & Wires Co., Ltd,
|
Place of Origin: | Henan, China (Mainland) |
Add to My Favorites | |
HiSupplier Escrow |
1.copper conductor, medium voltage, 300mm2
2. XLPE insulated
3.copper tape screen
4.steel tape armoured
5.PVC sheat
Use characteristic
1.installation temperature:≥0°C
2. long-term permissible operation temperature≤90°C
3.Under the condition of short circuit (the max. continuing time should not exceeding 5 seconds) the max. operation temperature:250°C
4.minimum bending radius:
single-core cable: 20D, mm
multicore cable: 15D, mm
Note: D means the actual outer diameter of cables
5. Suitable areas :
Direct burial in the ground and the capacity of bearing certain mechanical force, not proper in the pipeline
6.Main electrical characteristics
Item no. |
Uo/UKv Rated voltage
Techniques |
3.6/6 |
6/6 6/10 |
8.7/10 8.7/15 |
12/20 |
18/30 |
21/35 |
26/35 |
|
1 |
Ω/KM DCR |
Referenced by IEC60502-2:2005 |
|||||||
2 |
Regular part
Discharge test |
(kv) Inflicted voltage |
6.2 |
10.4 |
15 |
21 |
31 |
36 |
45 |
(pc) Discharge max.capacity |
10 |
10 |
10 |
10 |
10 |
10 |
10 |
||
|